Model TP-524D-HRT
TP-524D-HRT Instruction Manual Rev. 0.3 Page 8 of 48
Drain
Conduit
"T"
EYS Seal Fitting
PGM 1
PGM 2
MODEL TP-524D
HOUSTON, TEXAS
FLT 1 2 CAL
MicroSafe H2S Gas Sensor
ALM ALM
TM
Figure 7 Typical Installation
Any unused ports should be blocked with suitable ¾” male NPT plugs. Detcon
supplies one ¾” NPT male plug with each J-box enclosure. If connections are other than ¾”
NPT, use an appropriate male plug of like construction material.
2.6 Field Wiring
Detcon Model TP-524D-HRT solid-state H
2
S sensor assemblies require three conductor connections between
power supplies and host electronic controller’s 4-20mA / HART Interface. Wiring designations are DC+, DC-
, MA (sensor signal). A 250 ohm load resistor is needed on the 4-20 mA line when it is not being used. The
maximum wire length between sensor and 24VDC source is shown in the Table below. The maximum wire
size for termination in the Junction Box is 14 AWG.
Table 2 Wire Gauge vs. Distance
AWG Wire Dia. Meters Feet
Over-Current
Protection
22 0.723mm 700 2080 3A
20 0.812mm 1120 3350 5A
18 1.024mm 1750 5250 7A
16 1.291mm 2800 8400 10A
14 1.628mm 4480 13,440 20A
Wiring table is based on stranded tinned copper wire and is designed to serve as a
reference only.
Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.