1600A-N1R Instruction Manual Rev. 0.1 Page 4 of 38
3.0 Installation
Securely mount the Model 1600A-N1R in a suitable 19 inch rack. Allow at least 16” of depth for wiring.
19.00"
18.25"
8.75"
Model 1600A-N1P
Multi-Channel Gas Detection Control System
5.75"
Figure 3 Unit Mounting and Dimensional
Connect 110/220VAC input wiring to the terminals labeled “ACV (L1)”, “Neutral (L2)”, and “Ground” (See
Figure 4). The Power Supply is capable of handling AC inputs from 100-240VAC 50-60Hz without
degradation.
PLUGTRUB
O
I
5A
O
I
2A
O
I
2A
Ground
24VDC
VAC (L1)
NEU (L2)
Figure 4 AC/DC Inputs
If applicable, connect 24 VDC to the terminals labeled “24VDC” and “DC Comm”. This input can be used for
primary power or back-up power in the event of AC power failure.