Sentinel CX Sensor Station IM Rev. 1.2 Page 4 of 4
routes around congestion and line-of-sight obstacles while improving throughput as subscriber device
density increases.
The radio module is housed in a black ABS box mounted inside of the CX stainless steel enclosure. The
standard package includes two PCAs mounted inside the black ABS box (radio PCA and Smart battery
charging PCA), 5 dB antenna, and a protective antenna cover. The battery PCA includes circuitry to safely
recharge the battery from a 24VDC input and a fuel gauge circuit to monitor the charge remaining in the
battery.
The radio PCA includes a 2.4Ghz radio and a rotary switch for setting the RF channel of the system (Figure
2). Use a small screwdriver to rotate the switch until the arrow points to the desired RF channel number (16
channels available, 0h-Fh).
NOTE
All devices within the network must be on the same RF channel to operate correctly.
Each radio module is required to have a unique address. These addresses typically start at 01h and continue
sequentially for each SmartWireless CX in the gas detection system. The radio PCA includes a pair of
rotary switches to set this address (Figure 2).
NOTE
The switch for the most significant digit (MSD) is on the right and the least significant digit
(LSD) is on the left.
Figure 2 SmartWireless® CXT Radio Module
1.6 Sensor Inputs
The SmartWireless® CXT includes a Sensor Input PCA that accepts 4-20mA inputs from up to 4 attached
sensors. The PCA includes two rotary switches to set its Modbus address (Figure 3). This address is set to
01 for SmartWireless® systems using a CXT or Model X40 controller. If an MCX-32 controller is being
used, this address needs to be unique for each CXT in the system. For an MCX-32 system, the addresses
should start at 40h and continue sequentially for each CXT in the system.
Sensor Connector Ratings
Voltage: 9-11.2 VDC
Current: 100 mA max through any single sensor connector
RF Channel
Selector Switch
Modbus
Address LSD
Switch
Modbus
Address MSD
Switch